Question 6 of 59In order to save energy, you are going to install an automated system to switch off lights. What should be taken into consideration when installing such a system?
Correct Answer: D
Question 7 of 59You are working with a customer who requires a guarantee that THDi levels coming from the UPS should not exceed more than 3% THDi. Furthermore, he wants to run a power-efficient data center. The UPS has a 6-Pulse SCR/Thyristor based rectifier. The current load on the UPS is approximately 80%. The customer indicates they are not expecting any changes on the ICT infrastructure for the next 3 years. What should you recommend?
Correct Answer: C
Question 8 of 59What is a significant difference between a halocarbon gas-based fire suppression system and an inert gas-based fire suppression system?
Correct Answer: C
Question 9 of 59You are installing new copper cabling. What is the advantage or disadvantage of choosing pre-terminated category 6 or 6A cabling?
Correct Answer: A
Question 10 of 59You are allowed to use a calculator for this question. - A computer room has a net volume of approximately 2,500 m3/88,287 ft3. - The temperature is 20 °C/68 °F. - The required design concentration is 7%. - The S-Factor is 0.1359 (metric)/1.885 (imperial). Calculate the amount of gas required for this computer room based on FM200. What is the correct weight?